HGT соединительная клемма.
The heat shrink sleeve is made of polyolefin with superior clarity and hot melt adhesive, which provides excellent insulation protection, waterproofing and corrosion protection. The middle copper tube is a high purity copper tube with excellent electrical conductivity. It is often used to protect wires, wiring harnesses, and electronic connectors to improve locking and anti-vibration functions in harsh environments.
Shrinkage ratio 3;1, three colors: transparent red, transparent blue and transparent yellow.
PA hot melt adhesive has excellent waterproof performance.
Good transparency and good outer tube, high tensile strength, high elasticity, the tube is not easy to deform.
Excellent elongation properties and resistance to mechanical damage.
Make sure that the corrugated outer layer is not damaged and has good conductive properties.
Starting temperature: 60℃
Final shrinkage temperature: 100℃.
Working temperature: -45℃~105℃
Compliance with Standards: Certificates
Meet UL, ROHS, REACH
| Part Number
Product number |
heat shrink tube(mm) | Brass copper pipe(mm) | COLOR
color |
Cable Size | Packing | |||||
| ID
internal diameter |
O.D.
Outer diameter |
L
length |
O.D.
Outer diameter |
ID
internal diameter |
L
length |
A.W.G. | mm2 | Pcs/bag | ||
| HGT-01 | 4.7 | 5.8 | 36.0 | 3.8 | 1.7 | 15 | Transparent RED | 22-18 | 0.5-1.0 | 1000 |
| HGT-02 | 5.7 | 6.9 | 36.0 | 4.8 | 2.4 | 15 | Transparent BLUE | 16-14 | 1.5-2.5 | 1000 |
| HGT-03 | 6.7 | 8.0 | 42.0 | 5.7 | 3.6 | 15 | Transparent ELLOW | 12-10 | 4.0-6.0 | 500 |
| Product performance | Detection method | Test data | |
| Unaged | Tensile strength | room temperature
room temperature |
≧16.2MPa |
| Elongation
Elongation |
≧200% | ||
| Aging | Tensile strength
Tensile strength |
151℃/7 days
151℃/7 days |
≧11.6MPa |
| Elongation | ≧100% | ||
| Voltage withstand and breakdown voltage (Unaged)
Withstand voltage and breakdown voltage (not aged) |
room temperature
room temperature |
2500V,60sec,
No breakdown 2.5 kV, 60 seconds, no breakdown |
|
| Voltage withstand and breakdown voltage (aged)
Withstand voltage and breakdown voltage (aging) |
151℃/7 days
151℃/7 days |
Withstand 2.5KV for 1minute and breakdown at least half of unaged breaddown voltage
Withstand a voltage of 2.5 kV for 60 seconds, and the breakdown voltage should be at least half the breakdown voltage in the non-aging state. |
|
| Copper corrosion | pass | ||
| Copper stable | No sign of degradation Min.Elongation 100%
No degradation elongation ≥100% |
||
| cold bend | -39℃/4 hours | No crack | |
| Heatstroke | 200℃/4 hours | No crack | |